Wall Component | Materials |
Base wall system – Use either 1, 2, 3, 4, 5 or 6 | 1 – Concrete Base Wall
2 – CMU Base Wall 3 – One layer of 5/8″ Type X gypsum wallboard installed on the interior side of minimum 3 5/8″ deep, minimum 20 GA. galvanized steel studs spaced a maximum of 24″ O.C. 4 – One layer of 1/2″ MgO wallboard installed on the interior side of minimum 3 5/8″ deep, minimum 20 GA. galvanized steel studs spaced a maximum of 24″ O.C. 5 – FRT wood studs spaced maximum of 24″ O.C. with 5/8″ Type X gypsum wallboard installed on the interior side. 6 – FRT wood studs spaced maximum of 24″ O.C. with 1/2″ MgO wallboard installed on the interior side. |
Floorline Fire-stopping to Back Edge of Insulation Layer – Use either 1 or 2 | 1 – 4″ 4 pcf mineral wool (friction fit or installed with Z-Clips)
2 – FRT lumber – 1 1/2″ thick minimum. |
Cavity Insulation – Use either 1 or 2 | 1 – None
2 – Full or partial fill mineral wool. 3 – Full or partial fill fiberglass batts. |
Composite Exterior Sheathing – Use either 1, 2 or 3 | 1 – Maximum 3 3/4″ thick ArmorWall NC installed vertically or horizontally and attached directly to Base Wall System with insulation facing inward. Installed with a minimum #14-13 DP1 screws spaced 12″ O.C. vertically maximum at every stud.
2 – Maximum 4 1/4″ thick ArmorWall SP-NC Stuctural Insulated Sheathing™ installed vertically or horizontally and attached direclty to Base Wall System with insulation facing inward. Installed with a minimum #14-13 DP1 screws spaced 12″ O.C. vertically maximum at every stud. 3 – Maximum 3 3/4″ thick ArmorWall HD-NC Stuctural Insulated Sheathing™ installed vertically or horizontally and attached direclty to Base Wall System with insulation facing inward. Installed with a minimum #14-13 DP1 screws spaced 12″ O.C. vertically maximum at every stud. |
WRB Over Composite Exterior Sheathing | W. R. MEADOWS AIR-SHIELD LMP (gray)
W. R. MEADOWS AIR-SHIELD LMP (black) W. R. MEADOWS AIR-SHIELD TMP W. R. MEADOWS AIR-SHIELD LSR W. R. MEADOWS AIR-SHIELD SMP |
Exterior Cladding
Use either 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15 |
1 – Brick – nominal 4″ clay or concrete brick or veneer with maximum 24″ air gap behind the brick. Brick ties/anchors 2″ O.C. maximum.
2 – Stucco – minimum 3/4″ thick exterior cement plaster and lath. For systems that require a more durable WRB system, any building wrap or 15# felt that is not self-adhered asphalt or butyl based can be used as a slip sheet between the WRB and the lath. 3 – Limestone – minimum of 2″ thick using any standard non-open joint installation technique such as shiplap. 4 – Natural Stone Veneer – minimum 2″ thick using any standard non-open joint installation technique such as grouted/mortared stone. 5 – Cast Artificial Stone – minimum 1 1/2″ thick complying with ICC-ES AC 51 using any standard non-open joint installation technique such as shiplap. 6 – Terra Cotta Cladding – minimum 1 1/4″ thick (solid or equivalent by weight) using any standard non-open joint installation technique such as shiplap. 7 – Thin brick/cultured stone set in thin-set adhesive and metal lath that has been tested to ASTM E119 (brick exposed to furnace) and remains in place for a minimum of 30 minutes, or has passed an NFPA 285 test. Minimum 3/4″. For systems that require a more durable WRB system, any building wrap or 15# felt that is not self-adhered asphalt or butyl based can be used as a slip sheet between the WRB and the lath. 8 – TABS II Panel System with 1/2″ thick bricks using TABS Wall Adhesive. 9 – IQBrick™ thin brick panel system by MaxLife Industries. 10 – Any MCM/ACM that has successfully passed NFPA 285. 11 – Uninsulated sheet metal building panels including steel, copper, aluminum. 12 – Uninsulated fiber-cement siding. 13 – Stone/Aluminum honeycomb composite building panels that have successfully passed NFPA 285 criteria. 14 – Autoclaved-aerated concrete (AAC) panels that have successfully passed NFPA 285 criteria. 15 – Terra Cotta Cladding – any rain-screen terra cotta (min. 1/2″ thick) with ventilated shiplap. 16 – NFPA 285 approved EIFS (only with the WRB approved for the specific EIFS system). |
Window Perimeter
Use either 1, 2, 3, 4 or 5 |
1 – Minimum 1/2″ thick composite exterior sheathing, MgO, attached with 1 1/4″ long, Type S stainless steel screws, spaced max 2″ from corners and max 12″ O.C. to window studs to line window opening, covering full depth of exterior wall.
2 – Minimum 1/2″ thick composite exterior sheathing, MgO, attached with two ribbons of polyether adhesive, running continous across entire span of window opening to line window opening, covering depth of composite exterior insulated sheathing only leaving no foam exposed. 3 – When using steel stud walls, base wall window perimeter may be 20 GA C channel to line window perimeter of opening, covering depth of composite exterior insulated sheathing leaving no foam exposed. 4 – When using FRT stud walls, base wall window perimeter may be FRT to line window perimeter of opening, covering depth of composite exterior insulated sheathing leaving no foam exposed. 5 – When using concrete or CMU walls, steel or FRT framing may be added to wall window perimeter to line window perimeter of opening, covering depth of composite exterior insulated sheathing leaving no foam exposed. |
Pre-panelized Construction Panel Seaming
Use either 1 or 2 |
1 – Seams connecting two large prefabricated panels shall sandwich 2″ depth of 4 pcf mineral wool. Then cover joint with maximum 6″ wide seam tape.
2 – Seams connecting two large prefabricated panels shall install two continuous sealants consisting of noncombustible backer rod (such as 3M PM4) and sealed with Class A Silicone Building Sealant per ASTM E84. |
12-2020
Full NFPA testing documents are available. Please contact us to request these documents.